Questions and Answers
5 Questions
If i hook up 2 12v batteries in parallel ,how much time would this add to the run time for a 1/2h sump pump.
1. This depends on the battery capacity. Two 100Ah batteries connected in parallel would provide 200 × 12 × 0.9 / 375W = 5.76 hours of continuous runtime. However, a water pump cannot run continuously for that long; it would essentially drain the tank in about an hour. If this answer does not resolve your issue, please contact us again for assistance.
By vevor
Will this work for this buffering scenario? The UPS is plugged into 20A outlet that is also using 1500W for a heater while charging the UPS. While the power from the 20V outlet is still on the UPS's battery outlet powers a 1500W microwave, temporarily. The 20A outlet draws 1500W for the heater & the small amount to charge the UPS battery. The UPS battery provides the on demand 1500W for the microware while the 20A outlet power remains on. This way the total power isn't limited to the UPS output
A 20A socket can only supply power to devices with a power of 2400W, regardless of the location. It was sufficient for charging the battery with a 1500W UPS, but it might not have been enough to power the water pump at the time.
By vevor
Can I use 2-6v batteries in series for longer run times with the 3000w unit
Yes, you can connect two 6V batteries in series to get 12V. If this answer does not resolve your issue, please contact us again for assistance.
By vevor
Can the battery or batteries hooked up to this battery back up be solar charged also
That's possible. If this answer doesn't solve your problem, please contact us again for assistance.
By vevor
How long can the system run on one battery when there is a loss of power
This depends on the battery size. For example, a 100AH ​​battery * 12V = 1200W. If your water pump is 350W, then it would be 1200W / 350 * 0.9 = 3.08 hours/hour. If this answer does not solve your problem, please contact us again for assistance.